Skip to content
MoneyDeck

Voltage Drop Calculator

Check voltage drop and power loss over any wire run

Updated · US rules · Free, no signup

V

Line-to-line voltage for three-phase.

A

Distance from the source to the load, not the round trip.

Voltage drop

2.96 V

Voltage drop

2.47%

Voltage at load

117.04 V

Power lost in wire

44.4 W

Conductor area

3.31 mm²

Assessment

Good — within the 3% branch-circuit guideline

Voltage drop (%) by wire size for this run

About the Voltage Drop Calculator

This voltage drop calculator shows how much voltage is lost in a length of cable before it reaches the load. Enter the wire gauge, conductor material, one-way run length, load current and supply voltage, and it returns the drop in volts and as a percentage, the voltage left at the far end, and the power wasted as heat in the wire.

Electricians and DIYers use it to check long runs to a garage, shed, well pump, EV charger or outdoor lighting; solar and RV installers use it on low-voltage DC runs where a small drop is a big percentage. A chart compares the drop across neighbouring wire sizes so you can see how much upsizing helps.

The US National Electrical Code recommends (in informational notes) keeping drop to about 3% on a branch circuit and 5% total from service to load. The calculation uses NEC Chapter 9 conductor areas and resistivity at 75 °C, which is conservative for most installations.

With the default inputs, the voltage drop is 2.96 V. Change any value above to recalculate instantly.

How to use the voltage drop calculator

  1. 1Choose DC, single-phase or three-phase and enter the supply voltage.
  2. 2Enter the load current in amps.
  3. 3Enter the one-way distance from panel (or battery) to the load.
  4. 4Select copper or aluminum and the wire gauge.
  5. 5Check the percent drop — aim for 3% or less — and compare sizes in the chart.

Formula and method

Single-phase / DC: VD = 2 × K × I × L ÷ CM Three-phase: VD = √3 × K × I × L ÷ CM

The K method multiplies the conductor resistivity constant K by the current and the one-way length, then divides by the wire’s cross-sectional area in circular mils. Single-phase and DC circuits multiply by 2 because current flows out and back; balanced three-phase circuits use √3 instead.

K is 12.9 Ω·cmil/ft for copper and 21.2 Ω·cmil/ft for aluminum at a 75 °C conductor temperature, and circular-mil areas come from NEC Chapter 9 Table 8. Power lost in the wire is I² × R summed over the current-carrying conductors. The method ignores conductor reactance, which only matters for very large cables or low power factor loads.

VD
Voltage drop in volts
K
Resistivity constant: 12.9 (copper) or 21.2 (aluminum)
I
Load current in amps
L
One-way length in feet
CM
Conductor area in circular mils

Worked examples

15 A on 12 AWG copper, 50 ft at 120 V

VD = 2 × 12.9 × 15 × 50 ÷ 6,530 ≈ 2.96 V, or 2.47% of 120 V — inside the 3% guideline. About 44 W is dissipated as heat in the cable.

30 A on 10 AWG copper, 150 ft at 240 V

VD = 2 × 12.9 × 30 × 150 ÷ 10,380 ≈ 11.18 V, or 4.66% of 240 V. That is over 3% for a branch circuit, so 8 AWG would be the better choice for this distance.

60 A three-phase on 4 AWG aluminum, 200 ft at 480 V

VD = 1.732 × 21.2 × 60 × 200 ÷ 41,740 ≈ 10.56 V, only 2.2% of 480 V. Higher voltage keeps the percentage drop low.

20 A DC on 8 AWG copper, 10 m at 12 V

10 m is 32.8 ft. VD = 2 × 12.9 × 20 × 32.8 ÷ 16,510 ≈ 1.03 V — an 8.5% loss on a 12 V system, which is why low-voltage DC runs need much heavier cable.

Frequently asked questions

What is an acceptable voltage drop?+

The NEC informational notes recommend no more than 3% on a branch circuit and 5% total including the feeder. Sensitive electronics and low-voltage DC systems often target 2–3% or less.

Do I use one-way or round-trip length?+

Enter the one-way distance from the source to the load. The formula already multiplies by 2 for single-phase and DC circuits to account for the return conductor.

How do I reduce voltage drop?+

Use a larger wire gauge, shorten the run, switch from aluminum to copper, or use a higher supply voltage (for example 240 V instead of 120 V), which halves the current for the same power.

Why is voltage drop worse on 12 V systems?+

Voltage drop in volts depends only on current, length and wire size. The same 1 V drop is under 1% of 120 V but over 8% of 12 V, and low-voltage systems also draw more current for the same power.

Does voltage drop waste electricity?+

Yes. The lost voltage times the current is power turned into heat in the wire. On long, heavily loaded runs this can be tens of watts continuously, which a larger conductor reduces.

Related tools