About the R-Value Calculator
This R-value calculator adds up the thermal resistance of a wall, ceiling, floor or roof assembly built from layers — drywall, insulation, sheathing, rigid foam, brick or concrete. Pick a material and thickness for up to five layers, add any extra R-value from a product label, and choose whether to include the still-air films on each surface. It returns the total R-value, the U-factor (its reciprocal), the metric RSI and U-value, and the heat flow through a given area for a temperature difference.
It is useful for comparing insulation options, checking an assembly against an energy-code R-value requirement, or estimating how much adding exterior foam improves an existing wall. Material values are typical per-inch figures for common products; use the label value of the exact product when you have it.
Layers in series simply add up. The result is the center-of-cavity (clear-field) value: studs, joists and other framing conduct more heat than insulation, so the whole-wall R-value of a framed wall is usually 10–25% lower than the cavity figure. Continuous exterior foam is the usual way to reduce that thermal bridging.
With the default inputs, the total r-value is 18.11. Change any value above to recalculate instantly.
How to use the r-value calculator
- 1Pick the material and thickness of each layer from inside to outside.
- 2Set unused layers to “None”.
- 3Add any extra R-value from product labels.
- 4Keep air films on for a standard wall or roof calculation.
- 5Enter an area and temperature difference to see heat flow.
Formula and method
Thermal resistances of layers that heat must pass through one after another add directly, so the total R-value is the sum of each layer’s R per inch times its thickness, plus any fixed label values and the surface air films (R-0.68 inside, R-0.17 outside are standard design values). The U-factor is the reciprocal of the total R-value and gives heat flow in BTU per hour per square foot per °F.
Metric RSI is R × 0.1761 (m²·K/W), and the metric U-value is 1 ÷ RSI in W/m²·K. Steady-state heat flow is area × temperature difference × U. This is a one-dimensional, clear-field calculation: it ignores framing, gaps, compression and moisture, which all lower real-world performance.
- R
- Thermal resistance, ft²·°F·h/BTU
- U
- Thermal transmittance (U-factor), BTU/h·ft²·°F
- A
- Area in square feet
- ΔT
- Indoor minus outdoor temperature in °F
- Q
- Heat flow in BTU per hour
Worked examples
2×4 wall with batts, OSB and 1 in XPS
Drywall 0.5 × 0.9 = 0.45, fiberglass 3.5 × 3.2 = 11.2, OSB 0.4375 × 1.4 = 0.6125, XPS 1 × 5 = 5.0 and air films 0.85 add to R-18.11. The U-factor is 1 ÷ 18.11 = 0.0552, so 100 sq ft at a 40°F difference loses about 221 BTU/h.
Attic with 14 in of blown cellulose over drywall
Cellulose at R-3.5 per inch × 14 in = R-49, plus R-0.45 for the drywall = R-49.45 (films excluded). Over 1,000 sq ft with a 50°F difference the ceiling passes about 1,011 BTU/h.
8 in concrete wall with 2 in closed-cell foam
Concrete adds only 8 × 0.08 = 0.64, while 2 in of closed-cell foam adds 13.0. With air films the total is R-14.49, or RSI 2.55 and a metric U-value of about 0.39 W/m²·K.
Frequently asked questions
How do you calculate the total R-value of a wall?+
Add the R-value of every layer heat passes through in series — interior finish, cavity insulation, sheathing, exterior foam, siding — plus the inside and outside air films. Framing lowers the whole-wall value, so treat the sum as a clear-field figure.
What is the difference between R-value and U-factor?+
R-value measures resistance to heat flow; higher is better. U-factor measures how much heat flows through; lower is better. They are reciprocals for an assembly: U = 1 ÷ R, so R-20 equals U-0.05.
How do I convert R-value to metric RSI?+
Multiply the US R-value by 0.1761 to get RSI in m²·K/W, or divide RSI by 0.1761 to get R. An R-20 wall is RSI 3.52.
Do air gaps add R-value?+
A sealed, still air space adds roughly R-0.7 to R-1, more if one face is reflective foil. A ventilated or leaky gap adds almost nothing, which is why air sealing matters as much as insulation.
Why is my wall’s real R-value lower than the insulation label?+
Wood studs and plates (about R-1.25 per inch) make up 15–25% of a typical framed wall, letting heat bypass the insulation. Compressed or poorly installed batts and air leakage reduce performance further.
What R-value does my wall or attic need?+
Requirements depend on climate zone and code edition. The DOE and the IECC list recommended or required values, commonly R-13 to R-20+5 for walls and R-30 to R-60 for attics.